High-Voltage Reactive Power Compensation Devices

High-voltage local reactive power compensation devices for 6kV and 10kV systems, using capacitor banks, series reactors and automatic controllers. Units correct the power factor at the load, reduce line current and release transformer capacity. Each enclosure includes capacitors, reactors, fuses, discharge resistors and protection, assembled and routine tested before shipment.

Compensation Sized from Your Reactive Load

We build each compensation unit around the measured reactive load: capacitor rating, reactor percentage, switching steps and controller logic. Each cabinet includes discharge resistors, HRC fuses and over-voltage protection, and is routine tested for capacitance, insulation and switching. You receive the calculation sheet, the switching diagram and the test report.

High-Voltage Reactive Power Local Compensation Device

High-Voltage Reactive Power Local Compensation Device

sage certifications

Certified Quality You Can Verify

Every product is backed by CQC certification, ISO 9001, ISO 14001 and ISO 45001 management systems, plus type-test and inspection reports. Certificates and routine test records can be supplied with your shipment, and third-party inspection is welcome before delivery. Clear documentation, traceable testing and consistent quality control protect your project from acceptance delays and long-term compliance risk.
High-Voltage Reactive Power Local Compensation Device

High-Voltage Local Compensation at 6kV and 10kV

Connecting the capacitor bank at the 6kV or 10kV bus corrects the power factor before the load reaches the transformer, so transformer and cable losses fall as well. The cabinet includes capacitors, discharge resistors, fuses and the switching device, assembled and tested as one unit.
GGJ Low-Voltage Capacitor Compensation Cabinet

Automatic Step Control for Variable Loads

The controller follows the load and switches capacitor steps in and out to hold the target power factor. Step size, switching interval and the number of steps are set from the load profile, and vacuum contactors or thyristor switches are selected for the switching frequency the plant actually needs.

Reactive Power Compensation Buying Guide | Steps, Reactors and Control

1. Measure the reactive load before sizing

Start from the load profile, not from the transformer rating. Record the active and reactive power through a full production cycle, then calculate the kVAr needed to reach the target power factor. Oversizing causes leading power factor at light load, which raises voltage and can trip protection; undersizing leaves a penalty on the electricity bill.

2. Choose the compensation voltage and connection

High-voltage compensation connects at the 6kV or 10kV bus and corrects the load before it reaches the transformer, which reduces transformer and cable losses. Low-voltage compensation at 400V is easier to switch in small steps but does not relieve the transformer. The right level depends on the load location, the network layout and the utility metering point.

3. Add reactors for harmonic-rich networks

ConfigurationEffectWhen to use
Capacitor onlySimple correction at the fundamental frequencyClean networks with low harmonic content
Detuned reactor 7%Shifts resonance below the 5th harmonicNetworks with 5th and 7th harmonic loads
Detuned reactor 14%Shifts resonance below the 3rd harmonicNetworks with strong 3rd harmonic content

A capacitor bank on a harmonic-rich network can amplify the harmonic and fail early. Ask for a harmonic study, or at least the measured harmonic spectrum, before choosing the reactor.

4. Set the switching steps and controller

Automatic compensation divides the total kVAr into steps so the controller can follow the load without hunting. Confirm the step size, the number of steps, the switching interval and the controller target power factor. Vacuum contactors or thyristor switches are chosen for the switching frequency; frequent switching needs components rated for the duty.

5. Confirm protection, discharge and ventilation

Each capacitor step needs a fuse, a discharge resistor and over-voltage protection. Discharge resistors bring the terminal voltage down to a safe level within the specified time after switching off. The enclosure needs ventilation for the capacitor and reactor losses, and the internal temperature must stay within the capacitor rating.

6. RFQ checklist

  1. System voltage and measured reactive load
  2. Target power factor and required kVAr
  3. Harmonic spectrum and reactor percentage
  4. Number and size of switching steps
  5. Controller target, protocol and metering
  6. Enclosure, ventilation and installation location
  7. Quantity, destination and delivery date

Send the load data and harmonic measurements and the compensation design can be confirmed in one round.

Get a Tailored Quote

Share your drawing, voltage, current and quantity. Our engineers will confirm the configuration and send a clear quotation, usually within 24 hours. OEM customization is welcome.